specifications are subject to change without notice 1 ? for ac current/voltage measurement ? field adjustment capability ? for din-rail mounting ? degree of protection: ip 50 product description model range code measurement power supply setpoints rated output calibration ordering key cvt-din av5ad01x compact transducer for ac current/voltage measurements with field adjustment capabil- ity. the housing is for din-rail mounting and ensures a degree of protection of ip 50. energy management compact transducer for ac measurements type cvt-din av1/av4/av5 type selection power supply a: 24 vac, -15% +10%, 50/60 hz 1) b: 48 vac, -15% +10%, 50/60 hz 1) c: 115 vac, -15% +10%, 50/60 hz 1) d: 230 vac, -15% +10%, 50/60 hz (standard) 1) on request range code av1: 100 vac - 1 aac (max. 120 vac - 1.2 a) av4: 100 vac - 5 aac (max. 120 vac - 6 a) av5: 500 vac - 5 aac (max.600 vac - 6 a) rated output 1: analogue output 0 to 20 ma (standard) 2: analogue output 4 to 20 madc 1) 3: analogue output 0 to 10 vdc 1) 4: analogue output 0 to ? vdc 1) calibration x: standard calibration y: special calibration, use ??followed by requested value input specifications accuracy (@ 25 c 5 c, r.h. 60%) 0.5% f.s., (0.1 ln/un to 1 in/un) additional errors: the given accuracy already includes: frequency, power supply, output load influences humidity < 0.3%, 60% to 90% r.h. input frequency < 0.4%, 62 to 400 hz magnetic field < 0.5%, @ 400 a/m ripple 1% according to iec 60688-1 and en 60688-1 rated input av1: 1 a (1 v internal shunt/1 ? imp)/ 100 vac (200 k ? impedance) av4: 5 a (250 mv internal shunt/ 0,05 ? impedance) / 100 vac (200 k ? imp.) av5: 5 a (250 mv internal shunt/ 0,05 ? impedance) / 500 vac (1 m ? imp.) ac frequency range 48 to 62 hz overload protection cont.: current: 1.2 x rated input voltage: 1.2 x rated input for 1 s: current: 20 x rated input voltage: 2 x rated input
2 specifications are subject to change without notice warm-up time 15 minutes operating temperature 0 to 50 c (32 to 122 f) (r.h. < 90% non-condensing) storage temperature -10 to 60 c (14 to 140 f) (r.h. < 90% non-condensing) insulation reference voltage 300 v rms to ground insulation 2000 v rms between output and measuring input, output and supply input. 4000 v rms between input/output and ground dielectric strength 4000 v rms for 1 minute noise rejection cmrr 80 db, 48 to 62 hz emc en 50081-1, en 50082-1 cvt-din av1/av4/av5 dimensions general specifications ac supply 230 vac, -15% +10%, 50/60 hz (standard) 24 vac, 48 vac, 115 vac, -15% +10%, 50/60 hz (on request) power consumption 5 va supply specifications range/load 0 to 20 ma load: 500 ? 4 to 20 ma load: 500 ? 0 to 10 v load: 10 k ? 0 to 1 v load: 10 k ? adjustment easy field adjustment from 50 to 130% of the i/u inputs which can be modified with- out any calibrator being re- quested response time 300 ms typical temperature drift 200 ppm/ c output specifications safety standards safety requirements iec 601010-1, en 61010-1 product requirements iec 60688-1, en 60688-1 connector screw-type, max. 2.5 mm 2 wires housing dimensions 4-din modules, 58.5 x 89 x 71.5 mm material abs, self-extinguishing: ul 94 v-0 degree of protection ip 50 weight 300 g approx. (packing included) approval ce connections 230vac 115vac 48vac 24vac ~ ~ adjustment input: current (1) com. input: voltage output: 20ma .. output: 10v/1v ..... } + } + 1 3 4 5 6 8 10 11 12 cvt-din a-v ac/dc note measurement inputs current measurement: between current input and common (1) terminals; voltage measurement: between voltage input and common (1) terminals.
|